Three Phase Surge Arrester T2 T3 20KA 40KA SPD For Cold Northern Workshops
Product Summary
Wide-temperature 3+NPE surge arrester engineered for sealed high-temp cabinets and cold northern workshops, rated up to 80℃ versus standard 70℃ SPD limits, with consistent residual voltage and surge capacity in unventilated power enclosures and hot production lines. Dedicated low-temperature thermal ...
Product Custom Attributes
Three Phase Surge Arrester T2 T3
,20KA 40KA SPD for workshops
,Cold Northern SPD with warranty
Basic Properties
Trading Properties
Product Description
| Product features |
| ● Extended rated high-temperature limit reaching 80℃. |
| ● No false thermal tripping under -40℃ frigid ambient. |
| ● Stable residual voltage through hot-cold temperature cycles. |
| ● Integrated thermal release isolates faulty modules automatically. |
| ● Compatible with industrial cabinets with large temperature swings |
|
● Suitable for installation in LPZ 1 -2 and subsequent lightning protection zones , it is used as a fine lightning arrester for three-phase power supply systems . |
Specification

|
Based on criteria |
GB/T 18802.11-2020 |
|
|
SPD type |
T2,T3 |
|
|
SPD model |
SLV 20-385/3+NPE |
SLV 20-320/3+NPE |
|
Electrical parameters |
||
|
Nominal operating voltage Un |
220Vac(50Hz) |
|
|
Maximum continuous operating voltage Uc |
385Vac(50Hz) |
320Vac(50Hz) |
|
Nominal discharge current (8/20μs)In |
20kA |
20kA |
|
Maximum discharge current (8/20μs)Imax |
40kA |
40kA |
|
Voltage protection level In@Up |
L-N:≤1 .3kV N-E:≤1 .5kV |
L-N:≤1 .0kV N-E:≤1 .5kV |
|
L 123-N(3kA&6kV) Uoc |
≤600V |
≤800V |
|
Response time tA |
L-N:≤25ns N-E:≤100ns |
|
|
Protected mode |
L1,L2,L3-N,N-E |
|
|
Mechanical parameters |
||
|
Way to install |
DIN 35mm guide rail |
|
|
Screw torque |
5 N*m |
|
|
Strand length |
12mm |
|
|
Wiring cross-sectional area |
2.5mm²-32mm² |
|
|
Product size |
90mmx72mmx68mm |
|
|
Shell Material and Flame Retardant Rating |
Mineral nylon PA6 ,V0 |
|
|
Warning system |
||
|
Degradation indicator |
Green window: OK; red window: Fail |
|
|
Remote communication contact type |
Normally closed , normally open switching contact |
|
|
Remote communication contact switching capability |
125Vac/1A,125Vdc/0 .2A |
|
|
Work environment |
||
|
Installation site |
Indoor |
|
|
Outer shell protection rating |
IP20 |
|
|
Temperature range |
-40℃…+80℃ |
|
|
Humidity range |
Relative humidity ≤95% (max 40°C) |
|
FAQ
Q1: Does 80℃ rating allow continuous 80℃ non-stop operation?
A: It is the maximum rated operating point; consistent performance is guaranteed with basic cabinet ventilation.
Q2: Does the low-temperature release reduce normal surge diversion capacity?
A: The mechanism only activates upon module overheating failure, remaining inactive during standard lightning and switching transients.
Q3:Are cooling fans mandatory for high-temperature cabinet installation?
A:Not required for standard enclosures; auxiliary ventilation is recommended for fully sealed zero-airflow cabinets.
Contact Our Experts And Get A Free Consultation!
Our mission is to offer "High Quality" & "Good Service" & "Fast Delivery" to help our clients to gain more profits.