2 Wire Control Signal SPD 5Vdc 10kV PLC Sensor Industrial Analog Loop Protection

Product Summary

LS-CH Series 2-Wire Control Signal Lightning Arrester is designed for communication equipment such as dedicated communication lines, telemetry signals, measurement and control signals, PLC analog control systems, and 4-20mA current loops. Suitable for installation in LPZ 2-3 and subsequent lightning ...

Product Custom Attributes

Nominal Operating Voltage (Un):
5Vdc / 12Vdc / 24Vdc / 48Vdc
Maximum Continuous Operating Voltage (Uc):
6Vdc / 18Vdc / 32Vdc / 60Vdc
Shock Rating (X-X,X-C C2):
10kV/5kA
Shock Rating (X-X,X-C B2):
4kV(10/700μs)
Shock Rating (X-X,X-C D1):
2.5kA(10/350μs)
Voltage Protection Level (X-X @C2):
≤15V / ≤30V / ≤60V / ≤95V
Response Time (tA):
≤1ns
Load Current (IR):
500mA
Highlight:

Signal Surge Protective Device 5Vdc

,

2 Wire Control Signal SPD

,

Analog Loop Protection Signal SPD

Basic Properties

Place of Origin:
Guangdong Province.China
Brand Name:
LLH
Model Number:
LS-CH5
Document:

Trading Properties

Minimum Order Quantity:
1 piece
Price:
US $10/ Piece
Packaging Details:
box
Delivery Time:
7-15 days
Payment Terms:
L/C,D/A,D/P,T/T,Western Union
Supply Ability:
5000-10000 pieces/mouth

Product Description

LS-CH Series 2-Wire Control Signal Lightning Arrester is designed for communication equipment such as dedicated communication lines, telemetry signals, measurement and control signals, PLC analog control systems, and 4-20mA current loops. Suitable for installation in LPZ 2-3 and subsequent lightning protection zones, it provides full-mode fine protection for two signal lines.

Featuring a plug-in module design, the product allows for easy replacement without interrupting signal transmission. The multi-level protection circuit ensures high flow rate and low residual voltage, effectively shielding signal lines from lightning-induced surges and electrostatic discharge. With a line-to-line bandwidth of 3MHz, it supports high-speed signal transmission without distortion.

 

Product Features
● It can simultaneously protect four communication signal lines.
● Multi level protection, high flow rate, and low residual pressure.
● The module can be hot swapped and replaced without interrupting signal transmission.
● Suitable for installation in LPZ 2-3 and subsequent lightning protection zones, it is a lightning arrester for communicationequipment such as communication dedicated lines, telemetry signals, measurement and control signals, PLC analogcontrol systems, and 4-20mA current loops.


Product Specification


2 Wire Control Signal SPD 5Vdc 10kV PLC Sensor Industrial Analog Loop Protection 0

 

Standards
IEC 61643.21
Models
LS-CH5/4
LS-CH12/4
LS-CH24/4
LS-CH48/4
Parameter
Nominal operating voltage Un
5Vdc
12Vdc
24Vdc
48Vdc
Maximum continuous operating voltage Uc
6Vdc
18Vdc
32Vdc
60Vdc
X-X,X-C Shock rating C2
10kV/5kA
X-X,X-C Shock rating B2
4kV(10/700μs)
X-X Up@C2 
≤15V
≤30V
≤60V
≤95V
X-C Up@C2
≤500V
X-X Up@B2
≤10V
≤25V
≤45V
≤60V
X-C Up@B2
≤300V
Response time tA
≤1ns
Load current IR
500mA
Line to line bandwidth fG
3MHz
Protective Line
X1-X2,X3-X4,X1,X3-C,X2,X4-C

 

Mechanical parameters
 
Installation method
DIN Rail 35mm
Screw torque
1N*m
Strip length
10mm
Wiring cross-sectional area
0.5mm²-2.5mm²
Product size
90mmx75mmx12mm
Shell material and flame retardant grade
PC+ABS,UL 94 V-0
Installation location
Indoor
Shell protection rating
IP20
Temperature range
-40℃…+80℃
Humidity range
Relative humidity≤95%

 

Notices

1. Select the model based on the signal line's nominal operating voltage (5Vdc/12Vdc/24Vdc/48Vdc).

2. Use wiring with cross-sectional area 0.5mm²-2.5mm² and tighten screws to 1N·m torque.

3. The plug-in module design allows for easy replacement, but disconnect the signal line if possible during replacement.

4. Ensure reliable grounding with ground resistance ≤4Ω to guarantee surge diversion.

5. Avoid installing in environments with strong electromagnetic interference to prevent signal distortion.

6. Regularly inspect the module for loose connections or physical damage; replace if faulty.

 

FAQ

Q1: What is the difference between full-mode protection and line-line mode protection?

A1: Full-mode protection covers line-line and line-ground paths, while line-line mode only protects line-line paths. This product offers full-mode fine protection.

 

Q2: Can it be used for both DC and AC signal lines?

A2: It is specifically designed for DC signal lines (5Vdc/12Vdc/24Vdc/48Vdc). For AC signals, choose dedicated AC signal SPD models.

 

Q3: What is the load current capacity of the product?

A3: The maximum load current is 500mA, suitable for most industrial control signal lines.

 

Q4: Does the product require external power supply?

A4: No, it is passive and does not require external power supply, drawing minimal power from the signal line.

 

Q5: What is the service life of the product?

A5: Under normal operating conditions, the service life is 5-8 years. It may vary based on surge frequency and environmental factors.