Network Surge Protection Device 5V 12V 24V 48V Two Wire Control Signal Lightning Arrester

Product Summary

LS-CHE Series 2-Wire Control Signal Lightning Arrester (Line-Ground Mode) is designed for communication equipment such as dedicated communication lines, telemetry signals, measurement and control signals, PLC analog control systems, and 4-20mA current loops. Suitable for installation in LPZ 2-3 and ...

Product Custom Attributes

Standards:
IEC 61643.21
Nominal Operating Voltage (Un):
5Vdc / 12Vdc / 24Vdc / 48Vdc
Maximum Continuous Operating Voltage (Uc):
6Vdc / 18Vdc / 32Vdc / 60Vdc
Shock Rating (X-X,X-C C2):
10kV/5kA
Shock Rating (X-X,X-C B2):
4kV(10/700μs)
Shock Rating (X-X,X-C D1):
2.5kA(10/350μs)
Voltage Protection Level (X-C @C2):
≤15V / ≤30V / ≤60V / ≤95V
Response Time (tA):
≤1ns
Highlight:

Network Surge Protection Device 48V

,

Surge Protection Device 5V

,

Two Wire Control Signal Lightning Arrester

Basic Properties

Place of Origin:
Guangdong Province.China
Brand Name:
LLH
Model Number:
LS-CH5E
Document:

Trading Properties

Minimum Order Quantity:
1 piece
Price:
US $10/ Piece
Packaging Details:
box
Delivery Time:
7-15 days
Payment Terms:
L/C,D/A,D/P,T/T,Western Union
Supply Ability:
5000-10000 pieces/mouth

Product Description

LS-CHE Series 2-Wire Control Signal Lightning Arrester (Line-Ground Mode) is designed for communication equipment such as dedicated communication lines, telemetry signals, measurement and control signals, PLC analog control systems, and 4-20mA current loops. Suitable for installation in LPZ 2-3 and subsequent lightning protection zones, it provides line-ground mode fine protection for two signal lines.

Featuring a plug-in module design, the product allows for easy replacement without interrupting signal transmission. The multi-level protection circuit ensures high flow rate and low residual voltage, specifically optimizing line-ground surge protection. With a line-to-line bandwidth of 3MHz, it supports high-speed signal transmission without distortion.

 

Product Features
● The module can be replaced by plug-in without interrupting the signal transmission.
● Large flow rate, low residual pressure.
● Line-GND mode fine protection.
● Suitable for installation in LPZ 2-3 and subsequent lightning protection zones, it is a lightning arrester for communication equipment such as communication dedicated lines, telemetry signals, measurement and control signals, PLC analog control systems, and 4-20mA current loops.

Product Specification
Network Surge Protection Device 5V 12V 24V 48V Two Wire Control Signal Lightning Arrester 0

 
Standards IEC 61643.21
Models LS-CH5E LS-CH12E LS-CH24E LS-CH48E
Parameter
Nominal operating voltage Un 5Vdc 12Vdc 24Vdc 48Vdc
Maximum continuous operating voltage Uc 6Vdc 18Vdc 32Vdc 60Vdc
X-X,X-C Shock rating C2 10kV/5kA
X-X,X-C Shock rating B2 4kV(10/700μs)
X-X,X-C Shock rating D1 2.5kA(10/350μs)
X-X Up@C2 ≤30V ≤60V ≤120V ≤190V
X-C Up@C2 ≤15V ≤30V ≤60V ≤95V
X-X Up@B2 ≤20V ≤50V ≤60V ≤120V
X-C Up@B2 ≤10V ≤25V ≤45V ≤60V
Response time tA ≤1ns
Load current IR 500mA
Line to line bandwidth fG 3MHz
Protective Line X1-X2,X1-C,X2-C

 

Mechanical parameters
 
Installation method
DIN Rail 35mm
Screw torque
1N*m
Strip length
10mm
Wiring cross-sectional area
0.5mm²-2.5mm²
Product size
90mmx65mmx13mm
Shell material and flame retardant grade
PC+ABS,UL 94 V-0
Installation location
Indoor
Shell protection rating
IP20
Temperature range
-40℃…+80℃
Humidity range
Relative humidity≤95%

 

Notices

● This product adopts line-ground mode protection, suitable for scenarios where line-ground surges are the main threat.

● Select the model based on the signal line's nominal operating voltage (5Vdc/12Vdc/24Vdc/48Vdc).

● Use wiring with cross-sectional area 0.5mm²-2.5mm² and tighten screws to 1N·m torque.

● Ensure reliable grounding with ground resistance 4Ω to guarantee surge diversion (critical for line-ground protection).

● Avoid installing in environments with strong electromagnetic interference to prevent signal distortion.

● Regularly inspect the module for loose connections or physical damage; replace if faulty.

 

FAQ

Q1: What is the difference between line-line mode and line-ground mode?

A1: Line-line mode protects against surges between two signal lines, while line-ground mode protects against surges between signal lines and ground. This product optimizes line-ground protection.

 

Q2: Why is grounding critical for this product?

A2: Line-ground mode protection relies on effective grounding to divert surge energy; poor grounding will significantly reduce protection performance.

 

Q3: What is the load current capacity of the product?

A3: The maximum load current is 500mA, suitable for most industrial control signal lines.

 

Q4: Does the product require external power supply?

A4: No, it is passive and does not require external power supply, drawing minimal power from the signal line.

 

Q5: What is the voltage protection level for line-line surges?

A5: The line-line voltage protection level is 30V / 60V / 120V / 190V (depending on model), providing basic line-line surge protection while focusing on line-ground protection.